Eastron SDM530 - MT
The SDM530-MT measures and displays the characteristics of three phase four wires (3p4w) supplies, including voltage, frequency, current, power, active and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh. Maximum demand current can be measured over preset periods of up to 60 minutes. In order to measure energy, the unit requires voltage and current inputs in addition to the supply required to power the product.
SDM530MT-MT supports max. 100A direct connection, saves the cost and avoid the trouble to connect external CTs, giving the unit a cost-effective and easy operation. Built-in interfaces provides pulse and RS485 Modbus RTU outputs. Configuration is password protected.
-
Accuracy
- Voltage: 0-5% of range maximum
- Current: 0-5% of nominal
- Frequency 0·2% of mid-frequency
- Power factor 1% of unity (0.01)
- Active power (W) ±1% of range maximum
- Reactive power (VAr) ±1% of range maximum
- Apparent power (VA) ±1% of range maximum
- Active energy (Wh) Class 1 IEC 62053-21
- Reactive energy (VARh) ±1% of range maximum
-
Interfaces for External Monitoring
Three interfaces are provided:
- an RS485 communication channel that can be programmed via protocol remotely.
- an Pulse output(Pulse 1) indicating real-time measured energy.(configurable)
- an Pulse output(Pulse 2) The modbus configuration (Baud rate etc.) and the pulse output assignments (kW/kVArh, import/export etc.) are configured through the Set-up screens.
-
Pulse Output
The unit provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total / import/export
kWh or kVarh.
The pulse constant can be set to generate 1 pulse per:
- DFt=2.5 Wh/VArh
- 0.01 = 10 Wh/VArh
- 0.1 = 100 Wh/VArh
- 1 = 1 kWh/kVArh
- 10=10Wh/kVArh
- 100 = 100 kWh/kVArh
Pulse width: 200/100/60ms
Pulse output 2 is non-configurable. It is fixed up with active kWh. The constant is 400imp/kWh.
RS485 Output for Modbus RTU For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu: Baud rate 1200, 2400, 4800, 9600 Parity none (default)/odd/even Stop bits 1 or 2 RS485 network address nnn – 3-digit number, 001 to 247 Environment
- Operating temperature -25°C to +55°C*
- Storage temperature -40°C to +70°C*
- Relative humidity 0 to 90%, non-condensing
- Altitude Up to 2000m
- Warm up time 1 minute
- Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
Eastron SDM530 - MT Electricity Meter

Quantity | VAT not included in the price |
---|---|
1 | 91 EUR |
10 | 85 EUR |
100 | 77 EUR |